loader
  • Universal paperless colour recorder
  • Number of Channels up to 8.
  • designed with modern advanced SMT technology
  • Programmable and modular input.
  • To is designed with lower power consumption, high accuracy, universal use, and easy operation.
  • Measurement of process parameters such as temperature, humidity, pressure, flow, vibration, etc., in various industry applications.
  • Multiple input types of thermocouples and RTDS, voltage/current inputs and two-wire transmitters are field-selectable.
  • Every channel can have an independent input specification. All channels are equipped.
  • Digital adjustment and digital filtering functions, and each channel can be set differently.
  • Digital adjustment and filtering parameters.
  • High-performance hardware design greatly decreased the temperature drift and the interference between channels.
  • Provide high-accuracy compensation functions such as ice-point compensation, copper resistance compensation and thermostat compensation to thermocouple inputs.
  • Provide accurate internal calculation functions including addition, extraction, and multiplication.
  • Standard MODBUS Protocol, configured with SCADA, DCS, PLC, etc, flexibly
  • Two Relay alarm outputs with NO, 30vdc/3a, 220vac/3a
  • RS232 Printing port for mini printer
  • One channel isolated 4- 20ma retransmission output
  • Isolated auxiliary 24vdc power supply for transmitter, sensor and another device, max. 40ma
  • Every input channel has an independent low/high limit alarm that can be assigned to any alarm output.
  • Advanced communication function. Provide a high-accuracy and stable multi-channel analogue data sampling function to the host computer.
  • Allow to define up to 12 field parameters to be defined, and the user can freely customise the instrument.
  • Export the data via the USB port and get the file in  .dat form
  • Live monitoring of the data on its software via communication on a PC
  • Achieved ISO9001 and CE certificates, comply with the EMC standard, high reliability and stability.
  • The power and I/O terminals have passed the anti-interference test of 4KV/5KHz burst of pulses.
  • Input: Thermocouples: K, S, B, T, E, J, N, R, Pt100,Cu50, Cu100, 0-5V, 1-5V,0-10V 4-20mA, 0-10mA, 0~20mv, 0~60mV, 0~100mV, etc.
  • Re-Transmission Output: 4-20mA
  • Communication : RS-485/RS-232 Modbus
  • Transmitter Supply : DC 24V
  • Alarm function: High and low alarm, configurable separately for each channel
  • Alarm output : Relay contact output(NO or NC):250VAC/1A or 30VDC/1A
  • No contact discrete output (NO or NC): 250VAC/0.3A(transient current 1A)
  • Power supply : 100~240VAC/50Hz, 24VDC
  • Measurement accuracy : ±0.2%FS±1digit / ±0.3%FS±1digit (only for Cu50)
  • Temperature drift : ≤0.01%FS/°C (typical 50ppm/°C)
  • Electromagnetic compatibility : IEC61000-4-4, ±4KV/5KHz; IEC61000-4-5, 4KV
  • Isolation withstanding voltage : Between power, relay contact and signal terminals ≥ 2300VDC;
  • Between isolated electroweak signal terminals ≥ 600VDC
  • Response time : ≤1.5 seconds(if digital filter parameter is set as 0 or 1)
  • Automatic pilot time interval : Approx. 1.2s or 2s configurable
  • Power consumption : ≤6W
  • Work ambience : Temperature -10~+60°C, humidity ≤ 90%RH
  • Front panel dimension :  96×96mm
  • Model No. :  MPR800
Inquire Now